Falling pressure after a kitchen extension
The property
An Edwardian terraced house with a kitchen extension at the back, heated by underfloor loops in a screed floor from a manifold in a cupboard.
The problem
The boiler pressure dropped every couple of days. There was no damp, and no warm patch could be felt through the large porcelain tiles.
How we found it
Each loop was pressure tested alone at the manifold, and one dropped. With the floor left running warm for longer, thermal images showed heat spreading near the back doors; tracer gas confirmed the point.
The outcome
One tile was lifted over the marked spot. We replaced the damaged length of loop during the visit; the repair had its own price, separate from the detection.